Product Name:
Temperature Controller
Send
Enquiry
|
|
|
|
Technical Specification:
|
|
|
|
·
Power
90 - 250 VAC, 47
- 63 Hz, 12VA, 5W maximum
11 - 26 VAC /
VDC, SELV, Limited Energy, 12VA, 5W maximum
|
|
1. Resolution: 18 bits
2. Sampling Rate: 5 times /
second
3. Maximum Rating: -2 VDC minimum,
12 VDC maximum( 1
minute for mA input )
4. Temperature Effect: ±1.5
uV/ °C for all inputs except mA
input ±3.0 uV/ °C for mA
input
5. Sensor Lead Resistance
Effect:
T/C: 0.2uV/ohm
3-wire RTD: 2.6 °C/ohm of resistance difference of
two leads
2-wire RTD: 2.6 °C/ohm of
resistance sum of two leads
6. Burn-out Current: 200nA
7. Common Mode Rejection Ratio
(CMRR): 120dB
8. Normal Mode Rejection Ratio (NMRR
): 55dB
9. Sensor Break Detection:
Sensor open for TC, RTD and mV
inputs,
Sensor short for RTD input,
below 1 mA for 4-20 mA input,
below 0.25V for 1 - 5 V input,
unavailable for other inputs.
10. Sensor Break Responding Time:
Within 4 seconds for TC, RTD and
mV inputs,
0.1 second for 4-20 mA and 1 - 5
V inputs.
|
|
|
|
|
|
|
|
Type
|
Range
|
Accuracy@ 25 °C
|
Input Impedance
|
|
J
|
-120 ~ 1000 °C
(-184 ~ 1832 °F)
|
±2 °C
|
2.2MΩ
|
|
K
|
-200 ~ 1370 °C
(-328 ~ 2498°F)
|
±2 °C
|
2.2MΩ
|
|
T
|
-250 ~ 400°C
(-418 ~ 752°F)
|
±2 °C
|
2.2MΩ
|
|
E
|
-100 ~ 900 °C
(-148 ~ 1652 °F)
|
±2 °C
|
2.2MΩ
|
|
B
|
0 ~ 1800 °C
(32 ~ 3272 °F)
|
±2 °C
(200°C - 1800°C)
|
2.2MΩ
|
|
R
|
0 ~ 1767.8 °C
(32 ~ 3214 °F)
|
±2 °C
|
2.2MΩ
|
|
S
|
0 ~ 1767.8 °C
(32 ~ 3214 °F)
|
±2 °C
|
2.2MΩ
|
|
N
|
-250 ~ 1300 °C
(-418 ~ 2372 °F)
|
±2 °C
|
2.2MΩ
|
|
L
|
-200 ~ 900 °C
(-328 ~ 1652 °F)
|
±2 °C
|
2.2MΩ
|
|
PT100
(DIN)
|
-210 ~ 700 °C
(-346 ~ 1292 °F)
|
±0.4°C
|
1.3KΩ
|
|
PT100
(JIS)
|
-200 ~ 600 °C
(-328 ~ 1112 °F)
|
±0.4°C
|
1.3KΩ
|
|
mV
|
-8 ~ 70mV
|
±0.05%
|
2.2MΩ
|
|
mA
|
-3 ~ 27mA
|
±0.05%
|
70.5Ω
|
|
V
|
-1.3 ~ 11.5V
|
±0.05%
|
650KΩ
|
|
|
|
|
Output 1 / Output 2 :
|
|
Relay Rating : 2A/240 VAC, life cycles 200,000 for resistive load
Pulsed Voltage :
Source Voltage 5V, current limiting resistance 66Ω .
|
|
|
|
Linear Output Characteristics:
|
|
|
|
Type
|
Zero Tolerance
|
Span Tolerance
|
Load Capacity
|
|
4-20 mA
|
3.6-4 mA
|
20-21 mA
|
500Ω max.
|
|
0-20 mA
|
0 mA
|
20-21 mA
|
500Ω max.
|
|
0-5 V
|
0 V
|
5-5.25 V
|
10KΩ min.
|
|
1-5 V
|
0.9-1 V
|
5-5.25 V
|
10KΩ min.
|
|
0-10 V
|
0 V
|
10-10.5 V
|
10KΩ min.
|
|
|
|
|
·
Linear Output :
|
|
1. Resolution: 15 bits
2.
Output Regulation: 0.02 % for full load change
3.
Output Settling Time: 0.1 sec. (stable to 99.9 % )
4.
Isolation Breakdown Voltage 1000 VAC
5.
Temperature Effect : ±0.01 % of SPAN / °C
|
|
|
|
|
|
1. Rating:
1A / 240 VAC
2.
Inrush Current: 20A for 1 cycle
3.
Min. Load Current: 50 mA rms
4.
Max. Off-state Leakage: 3 mA rms
5.
Max. On-state Voltage : 1.5 V rms
6.
Insulation Resistance: 1000 Mohms min. at 500 VDC
7.
Dielectric Strength : 2500 VAC for 1 minute
|
|
|
|
|
|
1. Alarm Relay: Form C,Max.
rating 2A/240VAC, life cycles 200,000 for resistive load.
2. Alarm
Functions : Dwell timer,
Deviation High / Low Alarm,
Deviation Band High / Low
Alarm
Process High / Low Alarm
3. Alarm Mode :
Normal, Latching, Hold, Latching / Hold.
4. Dwell Timer :
0.1 - 4553.6 minutes
|
|
|
|
|
|
1. Interface: RS-232 (1 unit),
RS-485 (up to 247 units )
2. Protocol:
Modbus Protocol RTU mode
3. Address : 1 -
247
4. Baud Rate :
2.4 ~ 38.4 Kbits/sec
5. Data Bits : 7
or 8 bits
6. Parity Bit :
None, Even or Odd
7. Stop Bit : 1
or 2 bits
8. Communication
Buffer : 160 bytes
|
|
|
|
|
|
1. Output Signal: 4-20 mA, 0-20
mA, 0-1V, 0-5V, 1-5V, 0-10V
2. Resolution: 15
bits
3. Accuracy:
±0.05 % of span ±0.0025 %/ °C
4. Load
Resistance: 0 - 500 ohms ( for current output ),10 K ohm minimum ( for
voltage output )
5. Output
Regulation: 0.01 % for full load change
|
|
|
|
|
|
1. Dual 4-digit LED
Displays: Upper 0.4" ( 10 mm
)
Lower 0.31" ( 8 mm
)
2. Keypad :
4 keys
3. Programming
Port: For automatic setup, calibration and testing
4. Communication
Port: Connection to PC for supervisory control
|
|
|
|
|
|
1. Output
1: Reverse (heating ) or direct ( cooling )action
2. Output 2: PID
cooling control, cooling P band 50 ~ 300% of PB, dead band -36.0 ~ 36.0%
of PB
3. ON-OFF: 0.1 -
90.0 ( °F ) Hysterisis control ( P band = 0 )
4. P or PD: 0 -
100.0 % offset adjustment
5. PID: Fuzzy
logic modified, Proportional band 0.1 ~ 900.0°F ,
6. Integral
time: 0 - 3600 seconds ,
Derivative time 0 - 360.0 seconds
7. Cycle Time:
0.1 - 90.0 seconds
8. Manual
Control: Heat (MV1) and Cool (MV2)
9. Auto-tuning:
Cold start and warm start
10. Failure Mode: Auto-transfer
to manual mode while sensor break or
A-D converter damage
11. Ramping
Control: 0 ~ 900.0°F/minute or 0 ~ 900.0 °F/hour ramp rate
|
|
|
|
|
|
1. Function: First order
2. Time Constant:
0, 0.2, 0.5, 1, 2, 5, 10, 20, 30, 60 seconds programmable
|
|
|
- Environmental
& Physical :
|
|
1.
Operating Temperature : -10°C to 50°C
2. Storage
Temperature : -40°C to 60°C
3. Humidity : 0
to 90 % RH ( non-condensing )
4. Altitude :
2000m maximum
5. Pollution :
Degree 2
6. Insulation
Resistance : 20 Mohms min. ( at 500 VDC )
7. Dielectric
Strength : 2000 VAC, 50/60 Hz for 1 minute
8. Vibration
Resistance : 10 - 55 Hz, 10 m/s² for 2 hours
9. Shock
Resistance : 200 m/s² ( 20 g )
10. Moldings :
Flame retardant polycarbonate
11.
Dimensions :BTC-9100 ---48mm(W) X 48mm(H) X 116mm(D), 105 mm depth behind
panel
12.
Mounting: BTC-9100 ---panel
mount, cutout 45 X 45
13. Weight : ( mm ) BTC-9100 ---
150 grams
|
|
|
|
|
|
1. Safety :
UL 61010C-1 , CSA C22.2 No. 24-93 , EN61010-1 (IEC1010-1)
2. Protective
Class : IP65 front panel with additional option,
IP50 front
panel without additional option,
all indoor use,
IP 20 housing
and terminals with protective cover.
3. EMC :
EN61326
|
|
|
|
Features :
|
- Easy-to-use
- Fuzzy
modified PID heat & cool control
- Fast
A-D sampling rate (5 times/s)
- Universal
input (PT100, thermocouple) with high accuracy 18-bit A-D
- Analog
output (linear current or voltage) uses high accuracy 15-bit D-A
- RS-485
RS-232 interface
- Programming
port provided on board
- Support
manual control & auto-tune function
- Wide
variety of alarm mode selection
- Lockout
protection control
- Bumpless
transfer during failure mode
- Soft-start
ramp and dwell timer
- Bright
display stabilized with digital filter
- SEL
function allows to rearrange user menu
- UL/CSA/CE
approval
- High performance
with low cost
|
|
|